INSTALLATION GUIDELINES SERIES HEATING CABLES
PAGE 18
THERMON...The Heat Tracing Specialists
®
TEP0118U-1111
heating cable on
bourdon type meter
heating cable
Installation on pressure gauges
Note:
- The heating cables should not touch or cross one
another.
- When prescribed in design apply aluminium tape over
the heating cable.
- Min. bending radius of the heating cable is 5-6 x cable
diameter.
- One heating cable is installed over the gauge, the other
heating cable(s) continue(s) straight on.
FT fixing tape /
SS tie wire