INSTALLATION GUIDELINES SERIES HEATING CABLES
PAGE 13
THERMON...The Heat Tracing Specialists
®
TEP0118U-1111
heating cable
Installation on pumps
NPS
½" 12 600
¾" 20 900
1" 25 1200
1½ 40 1200
2" 50 1500
2½" 65 1800
3" 80 2100
4" 100 3000
6" 150 4800
8" 200 6600
10" 250 8400
12" 300 10000
14" 350 11800
16" 400 13800
18" 450 16200
20" 500 18000
TYPICAL CABLE ALLOWANCES
PER PUMP
(single pass) in mm
N
O
M
I
N
A
L
P
I
P
E
S
I
Z
E
P
U
M
P
DN
FT fixing tape /
SS tie wire
Note:
- The heating cables should not touch or cross one
another.
- When prescribed in design apply aluminium tape over
the heating cable.
- Min. bending radius of the heating cable is 5-6 x cable
diameter.
- Apply additional SS tie wire/fixing tape in such a way
that heating cable makes close contact with the pump.